Características:
Wide viewing angle 2 x 20 (40 character) alphanumeric
LCD and dedicated LEDs provide convenient panel
status information
Operation is programmable using a multi-function
keypad and the panel LCD or via service computer (PC)
RS-232 service port provides upload/download PC
access for panel configuration and event history logs
Software updates are via PC download
Convenient library of standard custom label terms
Standard on-board DACT provides: Contact ID, 3/1, 4/2,
BFSK, and SIA formats
WALKTEST silent or audible system test**
Voltage and current for both the battery charger and the
battery can be displayed at the front panel LCD
Addressable Devices:
Using IDNet communications, up to 200 addressable
TrueAlarm detection points or addressable device points
are available (see page 3 for details)**
Two Standard Notification Appliance Circuits (NACs):
Class A or Class B outputs with solid state overcurrent
protection per NAC, each rated for 2 A
Selectable for Simplex ® SmartSync two-wire
horn/strobe control or synchronized strobe control**
Standard Power Supply:
Provides 3 A maximum @ nominal 24 DC
Automatic input power selection operates with 120 VAC
or 240 VAC, 50 or 60 Hz
On-board temperature compensated battery charger for
up to 12.7 Ah batteries in cabinet (UL and ULC) and up
to 25 Ah batteries in separate cabinet (UL only)
Additional standard features:
Programmable Active Status Reminder
Two auxiliary relays
NACs, Relay outputs, and communications circuits
are power limited (AC input, battery circuits, and City
Circuit Module outputs are non-power limited)
Available with red or beige cabinet
UL listed to Standard 864
Available option modules:
Door mounted 24 LED annunciator (standard on ULC
models)
3 A Expansion Power Supply with two on-board 2 A
NACs that operate the same as standard NACs
City Interface Module and Auxiliary Relay Module
Remote LCD and LED/Switch Annunciators